The numerical simulation with staggered alternation locations and multi-flow directions on the thermal performance of double-layer microchannel heat sinks

Han Shen, Gongnan Xie, Chi Chuan Wang

Research output: Contribution to journalArticlepeer-review

45 Scopus citations

Abstract

The novel staggered flow alternation structure (SFAS) proposed in prior study has proved to be an efficient way in improving the overall thermal performance with acceptable pressure drop penalty in Double-layer Microchannel Heat Sinks (DMHSs). Based on the prior design, a further numerical investigation concerning the optimum location of SFAS in DMHSs is presented. The corresponding temperature fields, Nusselt number, flow fields, pressure drop and thermal characteristics are presented through verified computational mode. In addition, the effect of flow arrangements such as concurrent, upper-inlet/lower-inlet countercurrent arrangement on the thermal performance are studied in more details. The best thermal location of SFAS in the DMHSs is found to be based on the alterable locations and multi-flow directions. Yet, changing the location of staggered alternation structure does not lead to an appreciable rise of pressure drop penalty in DMHSs. However, the improvement in thermal performance for upper-inlet countercurrent arrangement is significant. Placing the SFAS in the middle of the DMHSs ensures the best overall thermal performance.

Original languageEnglish
Article number114332
JournalApplied Thermal Engineering
Volume163
DOIs
StatePublished - 25 Dec 2019

Keywords

  • Double-layer microchannel heat sinks
  • Local position
  • Multi-flow direction
  • Staggered flow alternation structure
  • Thermal resistance

Fingerprint

Dive into the research topics of 'The numerical simulation with staggered alternation locations and multi-flow directions on the thermal performance of double-layer microchannel heat sinks'. Together they form a unique fingerprint.

Cite this