跳到主要导航 跳到搜索 跳到主要内容

Study on fire safety assessment of nuclear grade activated carbon

  • Sen Chang
  • , Jian Li
  • , Kunjun Wang
  • , Yongguo Li
  • , Lili Zhang
  • , Jianli Chen
  • , Jingguo Liu
  • , Zexiang Chen
  • , Zhen Wang
  • , Jianrong Hou
  • , Dangui Qiu
  • , Baoliang Zhang
  • China National Nuclear Corporation
  • Northwestern Polytechnical University Xian
  • China Nuclear Power Engineering Co. Ltd.

科研成果: 期刊稿件 › 文章 › 同行评审

5 引用 (Scopus)

摘要

In order to further clarify the fire safety evaluation of nuclear grade activated carbon, thermal analysis combined with pore structure and phase analysis was adopted for coal-based activated carbon and coconut shell activated carbon used in nuclear power plants. On the basis of establishing the relative fire safety evaluation model by using four important parameters: activation energy (E), maximum mass loss rate (DTGp), maximum mass loss rate temperature (Tp) and rapid reaction percentage (A12), the O/C ratio and enthalpy (H) were further introduced into the evaluation model to calculate the relative fire safety factor (RFSF). The results show that O/C ratio and enthalpy have greater influence on the fire safety of activated carbon than porosity characteristics. The RFSF values of coal-based and coconut shell activated carbon are 1.33 and 1.08, indicating that fire safety is higher than that of impregnated coconut shell activated carbon.

源语言英语
期刊论文编号105080
期刊Progress in Nuclear Energy
卷169
DOI
出版状态已出版 - 4月 2024